Clean Power

Ukrainian (UA)English (United Kingdom)

The National Academy of Sciences of Ukraine


The Institute of Electrodynamics

About Institute

DOI: https://doi.org/10.15407/publishing2017.46.006

THE PREVENTION OVERVOLTAGE IN RESONANT MODES NONSINUSOIDALITY MAGISITRALNIH ELECTRIC NETWORK

V.V. Kuchanskyi
Institute of Electrodynamics of the National Academy of Sciences of Ukraine,
Peremohy, 56, Kyiv-57, 03680, Ukraine,
е-mail: kuvlad@yandex,.ru

Due to the rising role of overhead lines extra high voltage there is a need of application of modern electronic devices that allow controlling modes of bulk electricity system. The switching control unit Switchsync F236 is one of such devices which enables to connect and disconnect contacts of poles circuit breakers at required time. This function of Switchsync F236 can be used not only for interruption of short circuit. One of the objectives of application Switchsync F236 is prevention of resonance overvoltage occurrence at closing extra high voltage line on no-load autotransformer. Durable resonance overvoltages may cause damage of electrical power equipment. This kind of overvoltages is caused by properties of the network and can be eliminated by changing the ratio between the parameters of the network and its mode. Unlike switching overvoltages that exist centiseconds, resonance overvoltages not only occur unexpectedly, but they may go on for a long time until the automatic action or action of personnel will not change electrical schemes or mode. The resonant overvoltages are neglected when selecting insulation or parameters for high-voltage surge arrester as this protective measure is calculated to limit switching overvoltages, not to extinguish a long resonance process. Therefore, the probability and development of system accidents due to resonance overvoltages is significant. The importance of application and prevention of resonance ovevoltages caused research area which is presented in article. References 11, figures 5.
Key words: resonance overvoltages, control switching, simulation, nonsinusoidal mode.


1. Vasiliev A.N.. MATLAB. Tutorial. Practical approach. Saint Petersburg: Nauka i Tekhnika, 2012. 448 p. (Rus)
2. Dudurych O.B., Mavrin O.I., Pokrovskyi K.B. High-voltage isolation in tasks and control questions Lviv: Vydavnytstvo Nats. Universytetu Lvivska politekhnika. 2013. 188 p. (Ukr)
3. Kuznetsov V.G., Tugai Yu.I., Kuchanskyi V.V.. Selection of a resistance compensation reactor taking into account the influence of unsymmetry parameters of TL EHV. Pratsi Instytutu elektrodynamiky NAN Ukrainy. 2012. No 33. P. 13–17. (Ukr)
4. Kuznetsov V.G., Tugai Yu.I., Kuchanskyi V.V.. Application of an artificial neural network to determine the characteristics of abnormal overvoltages. Pratsi Instytutu elektrodynamiky NAN Ukrainy. 2012. No 31. P. 8–14. (Ukr)
5. Kuznetsov V.G., Tugai Yu.I, Kuchanskyi V.V. Investigation of an effect of transposition of extra-high voltage transmission lines on pathological overvoltages. Tekhnichna elektrodynamika. 2013. No 6. P. 51–56.  (Ukr)
6. Kuznetsov V.G., Tugai Yu.I., Kuchanskyi V.V., Shpolianskyi O.G. The study of even harmonic resonance overvoltage at the transmission line 750 kV. Pratsi Instytutu elektrodynamiky NAN Ukrainy. 2012. No 29. P. 20–26. (Ukr)
7. Kuznetsov V.G.,Tugai Yu.I., Kuchanskyi V.V. Overvoltage in the abnormal modes of extra-high voltage trasmission lines. Tekhnichna elektrodynamika. 2012. No 2. P. 40–41. (Ukr)
8. Starting and system tests of 750 kV power transmission at Khmelnitskaya APS. – Zheshuv: The research report. Vsesoyuz. nauch.-issled. institut elektroenergetiki. 1985. 92 p. (Rus)
9. L. M. N. de Mattos, A. M. P. Mendes, J. F. de Lima Filho, M. C. Tavares Enhanced Analysis of Oscillatory Undamped Overvoltages in Transformer Energization. Proceedings of International Conference on power systems Transients IPST 2013 in Vancouver. Canada, 18-19 July 2013. P. 55–61.
10. J. F. Piñeros, J. A. Vélez, J. M. Salas, O. Monroy, M. T. Gutiérrez, F. Montaño Undesired Trip of a 230 kV Transmission Line due to 500 kV/450 MVA Autotransformer Energization. Proceedings of International Conference on power systems Transients IPST 2013 in Vancouver. Canada, 18-19 July 2013. P. 45–50.
11. D. D. L. T. Barros, W. L. A. Neves, K. M. C. Dantas, D. Fernandes Jr., L. Fonseca Controlled Switching of Transmission Line with Series Compensation. Proceedings of International Conference on power systems Transients IPST 2013 in Vancouver. Canada, 18-19 July 2013. P. 5–8.